NSW Fire Safety Brief

The 2026 NSW
Fire Safety Mandate:
AS 1851 Becomes Law

Effective: 13 February 2026

"From February 2026, maintaining fire safety measures to AS 1851-2012 is the law in NSW, not just good practice. The question for every owner is whether their records can show it."
— Jamie

1. The End of the 'Set and Forget' Era

For years, many building owners treated AS 1851-2012 as best practice rather than a legal requirement. From 13 February 2026, that changed.

Section 81 of the Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 already required owners to maintain each essential fire safety measure: scheduled measures to the standard in the fire safety schedule, and original measures not on the schedule to their original standard. Section 81A, which applies from 13 February 2026, adds that the maintenance activities (inspection, testing and servicing) for each measure must be done in accordance with AS 1851-2012, unless an approved performance solution covers them.

Records must be kept on site for 7 years. The maximum penalty is 600 penalty units for a corporation and 300 for an individual. The duty sits with the owner, even when a contractor does the work.

Where AS 1851 Section 14 Fits

Section 14, "Emergency planning in facilities", applies where emergency planning is one of your building's essential fire safety measures. Where it does, it inspects the emergency plan and the elements developed under AS 3745. The six-monthly table covers:

  • ECO list and evacuation equipment
  • Training records against the emergency plan
  • ECO alarm response test and evacuation exercise
  • Evacuation diagrams and assembly areas

Action: check your fire safety schedule to see whether emergency planning is listed for your building.

2. The Annual Fire Safety Statement

Under section 89 of the Regulation, the owner must give an annual fire safety statement (AFSS) for the building. The statement relies on each essential fire safety measure being assessed by a competent fire safety practitioner.

Good maintenance records make that assessment straightforward. Gaps make it slow and uncertain. If you are unsure who runs your Emergency Planning Committee (EPC) or when it last met, sort that out well before your AFSS is due.

The AFSS doesn't list warden training itself. Where emergency planning is one of the building's essential fire safety measures, AS 1851 Section 14 inspects training records against the AS 3745 emergency plan, and AS 3745 clause 6.5.1.1 sets six-monthly skills retention for ECO members. Training is also a WHS duty: section 43 of the Work Health and Safety Regulation 2025 (NSW) requires the emergency plan to include information, training and instruction for relevant workers.

3. The Integrated Safety Loop Concept

Compliance Ready uses the 'Integrated Safety Loop' to keep hardware, people and paperwork aligned. Many buildings run a 'Broken Loop': the hardware is tested, but the emergency procedures are left behind.

An Integrated Safety Loop has three parts:

Technical Axis

AS 1851 servicing of each fire safety measure, measured against its baseline data.

Human Axis

Warden training (six-monthly, as AS 3745 recommends), exercises, and EPC meeting minutes.

Document Axis

Diagram currency (AS 3745 five-year review, plus six-monthly Section 14 inspection where it applies), AFSS and risk assessments.

If the human axis slips, for example no exercise or warden training for more than 6 months, the loop is broken. That gap can carry insurance and WHS consequences. After a fire, an insurer will ask for maintenance and training records, and gaps can complicate a claim.

4. Sector-Specific Notes

Different facilities face different rules on top of section 81A. Here is how we apply them:

01Diagrams (The 5-Year vs 6-Month Trap)

Many owners think a diagram is fine for 5 years (the AS 3745 review benchmark). Where Section 14 applies, evacuation diagrams are also inspected every six months for relevancy and compliance with the emergency plan (Table 14.4.2, item 1.5). If the floor plan has changed since the diagram was drawn, update it.

02Childcare Centres (Regulation 97)

Under regulation 97 of the Education and Care Services National Regulations, centre-based services must rehearse emergency and evacuation procedures every 3 months, and display a floor plan near each exit. A six-monthly building cycle does not replace that.

03Aged Care

Under the Aged Care Act 2024 and the strengthened Quality Standards, providers owe residents a duty of care. We recommend emergency plans include resident risk profiles, and that drills show wardens understand how to move high-care residents.

5. What This Means for Owners

Section 81A puts the maintenance standard into law, and the owner carries the duty. Where emergency planning is one of the building's essential fire safety measures, that includes the "soft" side of fire safety: the emergency plan, diagrams, ECO list and exercise records.

AS 1851-2012 clause 1.10 requires routine service to be conducted by competent persons. Where it finds a critical defect, AS 1851 requires it to be reported (clause 1.17). Make sure whoever services your measures is competent for each one, including emergency planning where it applies.

Warden training is a separate question. AS 3745 recommends six-monthly skills retention, and Section 14 checks training records against your emergency plan. If your plan promises six-monthly training, your records need to show it.

"Most owners we meet don't know who is on their EPC, let alone when it last met. That is the easiest gap to close, and one of the most important."

6. The Compliance Ready Assessment

Our assessment checks 12 points. It shows you where you stand before your AFSS is due:

  1. Fire safety schedule: is emergency planning listed as an essential fire safety measure?
  2. Diagram presence: diagrams on every level, near exits and decision points.
  3. Diagram review date: flag if older than 5 years (AS 3745).
  4. Diagram inspection: flag if more than 6 months old where Section 14 applies.
  5. Exercises: six-monthly where Section 14 applies; 3-monthly rehearsals for childcare (Reg 97).
  6. Warden training: flag if more than 6 months since the last skills retention session (AS 3745).
  7. First attack training: we recommend a refresher every 2 years (not a legal requirement).
  8. EPC knowledge: flag if the answer is "Unsure".
  9. EPC meetings: we recommend every 6 months, in step with the Section 14 cycle.
  10. Minutes: available and filed with your fire safety records.
  11. Competent persons: someone competent is engaged for each measure, including emergency planning where it applies.
  12. Risk assessment: reviewed alongside the emergency plan.

Conclusion: Make Your Records Do the Work

Section 81A makes AS 1851 the legal maintenance standard for NSW building owners. Compliance Ready helps you bring the emergency planning side up to the same level as the hardware.

Your action plan: check your fire safety schedule, then check your records. If you cannot produce minutes from an EPC meeting in the last 180 days, or your diagrams haven't been checked in 6 months, fix that first.

Check Your 2026 Status

Find out whether AS 1851 Section 14 applies to your building, and whether your records are ready.

Free site assessment & review

See where your facility stands

Choose a free on-site or online assessment — you decide what works best for your facility.

On-site or online

Review your arrangements with our specialists in the format that suits you.

Clear next steps

Identify documentation, training and facility priorities before they become costly gaps.

Your free review

Choose your time

Use our live calendar to book without back-and-forth emails.

Practical and focused

Get an informed view of your current emergency planning arrangements.

Free assessment. No obligation.

Reference Notes

EP&A (Development Certification and Fire Safety) Regulation 2021. Section 81: the owner must maintain each essential fire safety measure, to the standard in the fire safety schedule or, for original measures not on the schedule, to their original standard. Section 81A (from 13 February 2026): maintenance activities (inspection, testing and servicing) must be carried out in accordance with AS 1851-2012 unless an approved performance solution covers them; records kept on site for 7 years; maximum penalty 600 penalty units (corporation) or 300 (individual). Section 89: annual fire safety statement.

AS 1851-2012. Clause 1.10: routine service of fire protection systems and equipment shall be conducted by competent persons. Clause 1.17: reporting of critical defects. Section 14, Emergency planning in facilities: Table 14.4.2 (six-monthly) and Table 14.4.3 (yearly). Section 14 applies through section 81A where emergency planning is one of the building's essential fire safety measures.

Work Health and Safety Regulation 2025 (NSW), section 43: emergency plans. AS 3745-2010: Planning for emergencies in facilities (voluntary standard; recognised benchmark). This article is general information, not legal advice.